ROOMING HOUSE MANAGEMENT · COMPLIANCE RECORDS
Rooming House Compliance Records in Victoria: Minimum-Standards Evidence, Gas and Electrical Checks, Heating, Smoke Alarms and the Annual ESM Report (2026)
By Yan Zhu · Published · Updated
The short answer
Since 13 October 2026 a Victorian rooming house operator must keep records sufficient to show that every room, every facility or service and every common area it provides meets the rooming house minimum standards, and must produce them as soon as practicable when the Director of Consumer Affairs Victoria asks (Residential Tenancies Act 1997 ss 142BAA–142BAB; up to 150 penalty units, or 750 for a company, for failing to produce). The standards bind the operator whatever agreement a resident is on (s 142B; CAV). Three recurring duties sit around that record: a gas safety check and an electrical safety check at least every 2 years by a licensed or registered gasfitter and electrician, with the record given to a resident within 7 days of a written request (CAV); a fixed heater secured in every resident’s room since 1 December 2025, energy-efficient by 1 December 2030; and, where the occupancy permit or a maintenance determination lists essential safety measures, an annual essential safety measures report prepared within the 28 days before each anniversary, with the reports and maintenance records available within 24 hours of a request (Building Regulations 2018 regs 223–225).
| Item | When | Who | Evidence to keep | Source |
|---|---|---|---|---|
| Minimum-standards record for rooms, facilities, services and common areas | Whenever a room, facility or common area is provided; kept current | Operator | Dated check per room and per shared area, photos, invoices for each fix | RTA ss 142B, 142BAA, 142BAB; CAV |
| Gas safety check | At least every 2 years; as soon as possible if none in the 2 years before a resident moves in | Licensed or registered gasfitter, booked by the operator | Check record with the gasfitter’s licence number; kept until the next record exists; copy to a resident within 7 days of a written request | RTA s 142BA; Rooming House Standards Regulations; CAV |
| Electrical safety check | At least every 2 years | Licensed electrician | As for gas | Same |
| Fixed heater in every resident’s room | Since 1 December 2025; energy-efficient by 1 December 2030 | Operator | Make, model and rating per room; installation invoice | Rooming House Standards Regulations reg 9A; CAV |
| Smoke alarms | Hard-wired and maintained; a faulty alarm is an urgent repair | Operator | Electrician’s installation and maintenance records; test records | CAV; building’s ESM documents |
| Evacuation diagram (AS 3745) | Displayed in every resident’s room and every shared area | Operator | Photo per room, dated | CAV |
| Annual essential safety measures report | Within 28 days before each anniversary of the occupancy permit or maintenance determination | Building owner (signs) | Report in the approved form; 10 years of reports, schedules, determinations and maintenance records, producible within 24 hours | Building Regulations 2018 regs 223–225 |
| Exits and paths of travel | At all times | Occupier | Walk-through notes | Building Regulations 2018 reg 228 |
| Council registration | For the period the council sets, not more than 3 years; renew before expiry | Proprietor | Certificate and its conditions | PHW Act ss 67, 74 |
| Register of occupants | Continuously; kept 12 months after the last entry | Proprietor | Names and addresses, arrival and departure dates, kept securely | PHW Regulations regs 21, 23 |
The 13 October 2026 records duty: what “sufficient” looks like
Section 142BAA of the Residential Tenancies Act 1997, inserted by the Consumer Legislation Amendment Act 2025, has three limbs. An operator that provides a room to a resident must keep records sufficient to demonstrate that the room complies with the prescribed privacy, safety, security and amenity standards; one that provides a facility or service must keep records for that; one that gives access to a common area must keep records for that too. Section 142BAB requires the operator to produce those records, in the manner the Director specifies, as soon as practicable after a request. The Act lets the Director publish guidance on what records are sufficient, by a notice in the Government Gazette and online (s 142BAA(4)–(5)); check for one before you settle a format.
The standards themselves are older: s 142B forbids providing a room, a facility or service, or access to a common area that does not comply (150 penalty units for a person, 750 for a company), and Consumer Affairs Victoria states they apply “whether the resident has a rooming house agreement or an individual rental agreement”. What changed in October is the burden of proof: compliance now has to be shown on paper. Where this duty sits among the other dated changes, with a rooming-house column for each, is in OptimaRea’s dated checklist of Victorian rental law changes 2025–2027.
A record that does that job has four properties: it is per item (each room and each shared area, not “the house”), it is dated (what was checked, when, by whom), it carries evidence (a photo, a certificate, an invoice) and it records the fix and the re-check, not only the fault. The walk-through below is a checklist a manager can keep for each room and shared area.
The minimum-standards walk-through, area by area
Consumer Affairs Victoria’s rooming house minimum standards page (updated 14 October 2026) sets out the requirements below; the instrument is the Residential Tenancies (Rooming House Standards) Regulations 2023. This is the recurring operating check. What a new building has to include from day one — the build and fit-out specification — is DollarBuild’s room-by-room standards guide.
| Area | What to check and record |
|---|---|
| Resident’s room | Entry door lock operated by a key (including a fob or PIN) from outside and openable from inside without a key; at least two working power outlets free for the resident’s use; a window covering that gives privacy, can be opened and closed, and reasonably blocks light; a fixed heater secured to wall, floor or ceiling |
| Shared bathroom and toilet | A bolt or catch, or privacy latch, that locks from inside without a key (a cabin hook does not comply); a working shower with a 3-star or better shower head where one can be fitted |
| Shared kitchen | Food preparation area and sink; an oven and a four-burner cooktop for every 12 or fewer residents without their own; 400 litres of refrigerator for every 4 or fewer residents without a fridge, plus 28.5 litres for each additional resident; a lockable cupboard of at least 100 litres for each resident; food preparation areas used only for food preparation |
| Kitchen in a resident’s room | Food preparation area, sink, working oven and cooktop, a refrigerator of at least 80 litres and a 100-litre cupboard |
| Dining | Enough chairs for the largest number of residents who can occupy one room, and a table that fits them |
| Laundry | For every 12 or fewer residents: a trough or basin with hot and cold water, space and hot and cold outlets for a washing machine, a clothesline or dryer, and free access to a working washing machine |
| Safety | An AS 3745 evacuation diagram in each resident’s room and shared area; circuit breakers and switchboard-type RCDs on all outlets and circuits; gas and electrical checks every 2 years; hard-wired smoke alarms |
| Security | Each external window that opens can be secured without a key and has a working latch; each entrance has a lock operated by a key from outside and without a key from inside; the main entry has a window, peephole or intercom and a working external light |
| Amenity | Light suited to each room and corridor; natural light by day and artificial light at night in habitable rooms; ventilation complying with the Building Code of Australia |
| Building | Structurally sound and weatherproof; free of mould and damp caused by or related to the building structure; anchors on corded blinds and curtains |
Gas and electrical checks: every two years, per premises
Consumer Affairs Victoria states the cadence plainly: a gas safety check every 2 years by a licensed or registered gasfitter of all gas installations and fittings, and an electrical safety check at least once every 2 years by a licensed electrician. If no gas check was done in the 2 years before a resident moves in, one is to be completed as soon as possible. The gas check is defined in the Rooming House Standards Regulations — correct installation of cylinders, isolation valves, clearances, ventilation, restraints on cookers, flue condition and servicing of Type A appliances.
Records. The fitter’s or electrician’s record should show their name, business details and licence number, the date, the address and the result. Keep each record until the next one exists, keep the compliance certificate or invoice for any later gas work, give a resident a copy within 7 days of a written request, and produce the records to the Director on request (s 142BA). CAV encourages operators to lodge the certificates for each premises through myCAV, which saves being asked for them while they are current.
The checks are per premises, so a nine-room house has one gas record and one electrical record to show, not nine. The cadence matches the one that has applied to every residential rental agreement since 13 October 2026; OptimaRea’s rental safety checks guide covers the rental side.
A fixed heater in every room: 1 December 2025 and 1 December 2030
Since 1 December 2025 every resident’s room must have a fixed heater secured to a wall, floor or ceiling: electric ducted or electric hydronic heating, an electric non-portable heater, or a non-ducted air conditioner or heat pump rated 2 stars or more for heating (CAV; Rooming House Standards Regulations reg 9A). From 1 December 2030 it must be energy-efficient: a 2-star or better non-ducted reverse-cycle unit, or a ducted heat pump with a heating seasonal performance factor of 3.2 or more. Gas ducted or hydronic systems in good working order can stay until the end of their life, and an exemption may apply where heating already exists or installation is barred by heritage law or owners corporation rules.
Record the make, model and rating of the heater in each room, where it is, and its installation invoice — the room-level record s 142BAA asks for.
What does not apply. The rental minimum energy efficiency standards that start on 1 March 2027 amend the minimum standards for residential rental agreements. Rooming houses have their own standards instrument and their own heating timetable, so this page does not apply the 2027 rental standards to them. Whether a whole house let under an ordinary residential rental agreement, or a self-contained unit inside a rooming house, also picks up the 2027 rental standards is an open question to put to a lawyer or to Consumer Affairs Victoria.
Smoke alarms: hard-wired, maintained, urgent when faulty
Consumer Affairs Victoria states that rooming houses must have hard-wired smoke alarms, that residents must report a faulty alarm and must not remove or interfere with one, and that a rooming house operator told an alarm is not working must arrange its repair or replacement immediately as an urgent repair. A hard-wired alarm is installed by a qualified electrician.
The 12-monthly smoke-alarm test in s 68AA of the Residential Tenancies Act is a duty of a residential rental provider under Part 2. For a rooming house, the maintenance and testing of the fire safety systems — which can include the alarms in common areas — is set by the building’s own documents: the essential safety measures listed in the occupancy permit or a maintenance determination (below). Where those documents are silent, a documented test at least once a year, to the manufacturer’s instructions, is the sensible minimum to record.
The annual essential safety measures report: owner, operator and manager
Part 15 Division 1 of the Building Regulations 2018 applies to Class 1b buildings — the classification for most small boarding and rooming houses — and to larger Class 3 buildings (reg 213). Where an occupancy permit or a maintenance determination requires essential safety measures (exit lighting, fire extinguishers, alarm systems and the like), the owner must:
- maintain each one so it can fulfil its purpose (reg 226) and not remove it from its approved location except to inspect, test or maintain it (reg 227);
- ensure an annual essential safety measures report is prepared within the 28 days before each anniversary of the first occupancy permit or maintenance determination that required them (reg 223(1)); for a building constructed before 1 July 1994 with required measures, the anniversary is 13 June (reg 223(2));
- make the report signed by the owner, in the approved form, stating the address, including details of any inspection report and stating that the owner took all reasonable steps to keep each measure operating and maintained (reg 224); and
- make the last 10 years of reports, the maintenance schedules and determinations, and the records of every inspection, test, maintenance and repair available at the building within 24 hours of a request by the municipal building surveyor or the fire brigade’s chief officer (reg 225).
Each of those duties carries up to 20 penalty units. Separately, the occupier of a Class 1b building must keep every exit and path of travel to a road readily accessible, functional and clear (reg 228) — a daily matter in a shared house, where bikes and bins end up in corridors.
Who does what. The owner signs the report and is liable for maintenance; the operator and its manager keep the building in the state the report certifies. In a managed house the manager’s job is the calendar (the anniversary date, the contractor’s visits), access for the inspector, and the records file that has to be produced within a day. Whether a particular house has required essential safety measures at all depends on its occupancy permit or a maintenance determination — ask the relevant building surveyor if no one has the documents. Converting a building to a rooming house is a change of use that must comply with the regulations for the new use (reg 229); the build-side evidence is the builder’s and DollarBuild’s subject, not this page’s.
Council registration and the prescribed accommodation standards
The council registers the premises under the Public Health and Wellbeing Act 2008 for the period it sets, up to 3 years (ss 67, 74), and before deciding an application it may inspect and require alterations or improvements (s 73). The Public Health and Wellbeing (Prescribed Accommodation) Regulations 2020 are what the council inspects against:
- Bedroom size and occupancy (reg 11): no room under 7.5 m² may be used as a bedroom; for stays over 31 days, a bedroom under 12 m² holds one person, and a larger one two people plus one for every 4 m² above 12 m².
- Maintenance and cleanliness (regs 13–14): bedrooms, toilets, bathrooms, laundries, kitchens, living rooms and common areas in good working order, clean and in good repair; each bedroom, and any bathroom attached to it, cleaned after it is vacated and before the next occupier.
- Water, waste and refuse (regs 15–19): a continuous supply of hot and cold water; vermin-proof bins, regularly cleaned and emptied.
- Toilets and bathing (reg 20): at least one toilet, one bath or shower and one wash basin for every 10 people.
- Register of occupants (regs 21, 23): names and addresses and arrival and departure dates, kept 12 months after the last entry, with reasonable steps to protect the information.
Each of those carries up to 20 penalty units. The registered rooming houses register shows the registration and its conditions, so a condition imposed at the last inspection should be on the compliance calendar too.
The compliance file to ask a manager for
Whoever manages the house, one compliance file should be producible on request — and it is the file to ask a prospective manager to show you: the room-by-room and shared-area standards record with its photos and invoices; the current gas and electrical records and their due dates; the heater record for each room; the smoke-alarm and essential-safety-measures schedule from the building’s documents; the council registration and its conditions; and the occupant register. Copies go to a resident within the deadlines above, and the whole file to Consumer Affairs Victoria or the building surveyor when they ask. OptimaRea’s rooming house property management page states that its multi-tenancy tier (8.90% + GST of rent collected) keeps the premises’ gas, electrical and hard-wired smoke-alarm records, with copies to residents within 7 days of a written request, and creates the minimum-standards record in the first compliance cycle; its rooming house rent evidence guide lists the occupant register among the tier’s inclusions. Call +61 420 100 892 to talk through a house.
Questions operators ask about rooming house compliance records
What records must a rooming house operator keep from 13 October 2026?
Records sufficient to show that each room, each facility or service and each common area it provides meets the rooming house minimum standards (Residential Tenancies Act 1997 s 142BAA), produced as soon as practicable when the Director of Consumer Affairs Victoria asks (s 142BAB; up to 150 penalty units, 750 for a company). Gas and electrical check records are kept under s 142BA and the Rooming House Standards Regulations.
How often are gas and electrical safety checks needed in a rooming house?
At least every 2 years each, by a licensed or registered gasfitter and a licensed electrician; if there was no gas check in the 2 years before a resident moves in, one is done as soon as possible. Keep each record until the next one exists and give a resident a copy within 7 days of a written request (Consumer Affairs Victoria).
Does every rooming house need an annual essential safety measures report?
Only where an occupancy permit or a maintenance determination requires essential safety measures for the building, or where a building constructed before 1 July 1994 had required measures (Building Regulations 2018 reg 223). Then the report is prepared within the 28 days before each anniversary, and 10 years of reports and maintenance records must be available within 24 hours of a request (reg 225).
Who signs the annual ESM report — the owner or the manager?
The owner of the building signs it (Building Regulations 2018 reg 224) and is responsible for maintaining each essential safety measure (reg 226). The operator and its manager keep the building in the state the report certifies; the occupier must keep the exits and paths of travel clear (reg 228).
Do the 2027 minimum energy efficiency standards apply to rooming houses?
The standards starting on 1 March 2027 amend the minimum standards for residential rental agreements; rooming houses have their own instrument, with a fixed heater in each room since 1 December 2025 and an energy-efficient one by 1 December 2030. Whether a whole house let under a residential rental agreement also picks up the 2027 standards is an open question for a lawyer or Consumer Affairs Victoria.
What does the council check when it inspects a rooming house?
The Public Health and Wellbeing (Prescribed Accommodation) Regulations 2020: bedroom size and occupancy (no bedroom under 7.5 m²), maintenance and cleanliness, hot and cold water, rubbish, at least one toilet, one bath or shower and one basin per 10 people, and the register of occupants. The council can require alterations before it registers or renews (Public Health and Wellbeing Act 2008 s 73).
Primary sources checked 29 November 2026
Each statutory statement names its section and links the authorised version or the regulator page it was read from on 29 November 2026. Penalty-unit amounts use the 2026–27 value of $209.10 and change every 1 July. Nothing on this page states what a room earns, how fast a room lets or what a house returns. Fees are OptimaRea’s published rates.
- Residential Tenancies Act 1997 (Vic), Authorised Version 115 (as at 13 October 2026) — Part 3 (rooming houses), ss 92–142ZV ↗
- Consumer Affairs Victoria — Rooming house minimum standards (last updated 14 October 2026): record keeping from 13 October 2026, the room, kitchen, laundry, bathroom and general standards, heating ↗
- Residential Tenancies (Rooming House Standards) Regulations 2023 (in-force consolidation) ↗
- Consumer Affairs Victoria — Rooming house operators: gas and electrical safety obligations (last updated 7 April 2021) ↗
- Consumer Affairs Victoria — Smoke alarms and fire safety in rental properties (last updated 27 February 2026) ↗
- Building Regulations 2018 (Vic), Version 032 (as at 27 October 2026) — Part 15 Division 1, regs 213, 223–228 (essential safety measures); reg 229 (change of use) ↗
- Public Health and Wellbeing Act 2008 (Vic), Authorised Version 071 (as at 30 September 2026) — ss 67, 71, 73, 74 (registration of prescribed accommodation) ↗
- Public Health and Wellbeing (Prescribed Accommodation) Regulations 2020, Version 005 (as at 1 July 2024) — regs 10, 11, 13–15, 18–23 ↗
- Consumer Affairs Victoria — Running your business: rooming house operators (last updated 14 October 2026): licence display, advertising, resident register, bonds, utilities, repairs, bond claims ↗
- Consumer Affairs Victoria — New changes to the rental laws (last updated 14 October 2026): the dated 2025–2027 commencements ↗
- Department of Treasury and Finance — Notice fixing the value of a penalty unit: $209.10 for the financial year from 1 July 2026 ↗
Continue with the rooming house guides
- Does a rooming house manager need a licence? The operator licence and the relevant person →
- Rooming house agreements and notices: residency rights, bonds, entry and disputes →
- Rooming house utilities, house rules and common areas →
- Changing a rooming house manager or operator: the BLA notice and the handover →
- Screening rooming house applicants and turning over a room →
- Rooming house property management in Melbourne — fee, inclusions, how a house moves to OptimaRea →
- Rental safety checks in Victoria: electrical, gas and smoke alarms →